TCM350

Standard Specifications
– Heavy duty, water cooled diesel engine
– Radiator with mechanical fan
– Protective grille for rotating and hot parts
– Electric starter and charge alternator
– Starting battery (with lead acid) including rack and cables
– Engine coolant heater
– Steel base frame and anti-vibration isolators
– Spare external fuel tank (open set)
– Flexible fuel connection hoses
– Two bearing, class H alternator
– Industrial exhaust silencer and steel bellows supplied separately
– Static battery charger
– Radiator with mechanical fan
– Protective grille for rotating and hot parts
– Electric starter and charge alternator
– Starting battery (with lead acid) including rack and cables
– Engine coolant heater
– Steel base frame and anti-vibration isolators
– Spare external fuel tank (open set)
– Flexible fuel connection hoses
– Two bearing, class H alternator
– Industrial exhaust silencer and steel bellows supplied separately
– Static battery charger
Dimensions and Weight
| Open Type |
Dry Weight |
Lenght |
Width |
Height |
Tank Capacity (L) |
|
|
750 |
1150 |
600 |
1000 |
– |
|
Canopy |
Dry Weight |
Lenght |
Width |
Height |
Tank Capacity (L) |
|
|
1350 |
2800 |
1000 |
1500 |
– |
Alternator Specifications
| Make | Leroy Somer | |
| Frequency | Hz | 50 |
| Design | Brushless, 2 poles | |
| Phase | 3 | |
| Voltage | V | 400/230 |
| Current | A | 0 |
| Insulation Class | H | |
Diesel Engine Specifications
| Manufacturer | Cummins | |
| Model | NTA855-G4 | |
| No. of Cylinders and Build | 3 Cylinder, In Line | |
| Aspiration and Cooling | Turbo Charged | |
| Maximum Standby Power | 1500 rpm | 45.6 kW [61.1 HP] |
| Total Displacement | L | 3.3 |
| Bore and Stroke | mm | 105×127 |
| Compression Ratio | 17.25:1 | |
| Rated Speed (rpm) | rpm | 1500 |
| Governor | Mechanical | |
| Oil Capacity | L | 8.3 |
| Coolant Capacity | L | 10.2 |
| Intake Air Flow | m³ /min. | 2.9 |
| Radiator Cooling Air | m³ /min. | 53 |
| Exhaust Gas Flow | m³ /min. | 7 |
| Start System | 12 | |
| Fuel Consumption | %100 (L/h) | 10.7 |
3 Phase Ratings, 50 Hz, PF 0,8
| Voltage | Standby Rating (ESP) | Prime Rating (PRP) | |||
| kVA | kW | kVA | kW | Amp | |
| 400/230 | 50 | 40 | 45 | 36 | 64 |
Standby Rating (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528. Overload is not allowed.
Prime Rating (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation,in accordance with ISO 3046.