TCM450Q

Introduction

Heavy duty, water cooled diesel engine Radiator with mechanical fan Protective grille for rotating and hot parts Electric starter and charge alternator Starting battery (with lead acid) including rack and cables Engine coolant heater Steel base frame and anti-vibration isolators Spare external fuel tank (open set) Flexible fuel connection hoses Two bearing, class H alternator Industrial exhaust silencer and steel bellows supplied separately Static battery charger Manual for application and installation

ISO 9001 This generator set is manufactured in facilities certified with ISO 9001.
 This generator set is available with CE certification.

3 Phase Ratings, 50 Hz, PF 0,8

Voltage Standby Rating (ESP) Prime Rating (PRP)
kVA kW kVA kW Amp
400/230 450 360 64

Standby Rating (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528. Overload is not allowed.

Prime Rating (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation,in accordance with ISO 3046.

Diesel Engine Specifications

Manufacturer Cummins
Model QSZ13-G3
No. of Cylinders and Build 3 Cylinder, In Line
Aspiration and Cooling Turbo Charged
Maximum Standby Power 1500 rpm 45.6 kW [61.1 HP]
Total Displacement L 3.3
Bore and Stroke mm 105×127
Compression Ratio 17.25:1
Rated Speed (rpm) rpm 1500
Governor Mechanical
Oil Capacity L 8.3
Coolant Capacity L 10.2
Intake Air Flow m³ /min. 2.9
Radiator Cooling Air m³ /min. 53
Exhaust Gas Flow m³ /min. 7
Start System 12
Fuel Consumption %100 (L/h) 10.7

Alternator Specifications

Make Leroy Somer
Frequency Hz 50
Design Brushless, 2 poles
Phase 3
Voltage V 400/230
Current A 0
Insulation Class H

Dimensions and Weight

Open Type

Dry Weight
(kg.)

Lenght
(mm.)

Width
(mm.)

Height
(mm.)

Tank Capacity (L)

750

1150

600

1000

Canopy

Dry Weight
(kg.)

Lenght
(mm.)

Width
(mm.)

Height
(mm.)

Tank Capacity (L)

1350

2800

1000

1500

Standard Specifications

– Heavy duty, water cooled diesel engine
– Radiator with mechanical fan
– Protective grille for rotating and hot parts
– Electric starter and charge alternator
– Starting battery (with lead acid) including rack and cables
– Engine coolant heater
– Steel base frame and anti-vibration isolators
– Spare external fuel tank (open set)
– Flexible fuel connection hoses
– Two bearing, class H alternator
– Industrial exhaust silencer and steel bellows supplied separately
– Static battery charger
– Manual for application and installation