TPE135

Introduction

Heavy duty, water cooled diesel engine Radiator with mechanical fan Protective grille for rotating and hot parts Electric starter and charge alternator Starting battery (with lead acid) including rack and cables Engine coolant heater Steel base frame and anti-vibration isolators Spare external fuel tank (open set) Flexible fuel connection hoses Two bearing, class H alternator Industrial exhaust silencer and steel bellows supplied separately Static battery charger Manual for application and installation

ISO 9001           This generator set is manufactured in facilities certified with ISO 9001.
               This generator set is available with CE certification.

3 Phase Ratings, 50 Hz, PF 0,8

 Voltage  Standby Rating (ESP)  Prime Rating (PRP)
 kVA  kW  kVA  kW  Amp
 400/230  150  120  137  110  198.5

 

Standby Rating (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528. Overload is not allowed.

Prime Rating (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation,in accordance with ISO 3046.

 

Diesel Engine Specifications

 Manufacturer  Perkins
 Model  1006TAG
 No. of Cylinders and Build  6 Cylinder, In Line
 Aspiration and Cooling  Turbo Charged
 Maximum Standby Power 1500 rpm  137.5 kW [184.5 HP]
 Total Displacement  L  5.99
 Bore and Stroke  mm 100×127
 Compression Ratio  17.0:1
 Rated Speed (rpm) rpm  1500
 Governor  Mechanical
 Oil Capacity  L  16
 Coolant Capacity L  37.22
 Air Intake Way Naturally Aspirated
 Mean Piston Speed m/s  6.35
 Exhaust Gas Flow m³ /min.  25.71
Engine coolant flow                                     L/min  140
 Fuel Consumption  %100  Prime power (L/h)  31.5

Alternator Specifications

Make Leroy Somer
Frequency  Hz  50
Design  Brushless, 2 poles
Phase  3
Voltage  V  400/230
Current  A  0
Insulation Class  H

Dimensions and Weight

 Open Type Dry Weight
(kg.)
 Lenght
(mm.)
 Width
(mm.)
 Height
(mm.)
 Tank Capacity (L)
   1150  2250  820  1450  –
 Canopy Dry Weight
(kg.)
 Lenght
(mm.)
 Width
(mm.)
 Height
(mm.)
 Tank Capacity (L)
   2100  3400  1120  1750  –

Standard Specifications

– Heavy duty, water cooled diesel engine
– Radiator with mechanical fan
– Protective grille for rotating and hot parts
– Electric starter and charge alternator
– Starting battery (with lead acid) including rack and cables
– Engine coolant heater
– Steel base frame and anti-vibration isolators
– Spare external fuel tank (open set)
– Flexible fuel connection hoses
– Two bearing, class H alternator
– Industrial exhaust silencer and steel bellows supplied separately
– Static battery charger
– Manual for application and installation